Twelve years ago I had that chap called Ed Davey, who happened to be the Energy Secretary


00:04.720 --> 00:09.760
at the time, standing in my living room, proudly telling him that I'd put enough solar on my roof


00:09.760 --> 00:14.400
that I would be able to cover our electricity all the year round and we basically wouldn't have


00:14.400 --> 00:22.400
much energy bills, whatever, but we'd be carbon neutral. And I achieved it ... on the 29th of November


00:22.400 --> 00:27.040
last year. So it took 12 years from getting ready to getting through, because [the] Renewable


00:27.040 --> 00:34.960
Heat Incentive didn't work right. And even if we take a slightly less harsh view, when I applied


00:34.960 --> 00:41.680
to Octopus for a quote, I think it was in April of last year and it took until November,


00:41.680 --> 00:45.600
And I had to really push, and because we don't turn our heating on until December,


00:45.600 --> 00:53.120
that was just in time. So I have a strong view, which I'm about to write in an open letter to the


00:53.120 --> 00:58.720
Secretary of State and to Greg of Octopus, that it ought to be possible for most people to put it


00:58.720 --> 01:03.440
in two days. And even in a distress purchase in the middle of winter, you're not just tempted to


01:03.440 --> 01:11.760
slap another gas boiler on the wall. So does it work? Is it saving? Was it quick? So here was my


01:11.760 --> 01:20.320
simple answer. Yes, yes. NO! 12 years, a bit slow. Does it work? Yes. So it went in on the 28th


01:20.320 --> 01:24.400
actually, it was officially commissioned on the 29th, and we've been warm and had hot water and


01:24.400 --> 01:31.680
stuff since then. Now they managed to install it with some interesting faults. So I spent quite


01:31.680 --> 01:38.800
a lot of time fighting it to start with, but absent those faults, it's been fine. We have not


01:38.800 --> 01:43.600
had no hot water. We have not been cold. I mean, I've been tweaking with the settings. So if you


01:43.600 --> 01:49.759
ask my other half, she might have a slightly different view, but that's one, that's an arguable one.


01:58.160 --> 02:02.400
So it does its job.  It did take two months to diagnose a fairly major installation fault.  On the other hand, the system was robust that it ran for two months with a fairly major installation


02:02.400 --> 02:13.120
fault. [] So Octopus came and did some sums. They didn't really pay attention to the insulation works I'd done and so they came out with a figure for heat loss and thus the the size of a heat pump we need which I said "That's out by a factor of two [] at least."  Being the sad git that I am I have half-hour gas readings


02:28.000 --> 02:32.240
through the coldest days we ever had in this house. So I can tell you exactly what we ... anyway,


02:32.240 --> 02:35.920
they're not allowed to take that into consideration, but they went and did their sums again and said "Oh yes, you're so right!" So in the end we only swapped out one radiator, and actually I should have let them


02:40.880 --> 02:46.000
put a slightly bigger one in [there]. But the really peculiar thing, the outside unit doesn't make any [noise] ... 


02:47.360 --> 02:51.760
It's like having an oscillating fan [whoosh, whoosh] noise; when it's getting really flat out it's like [WHOOSH]...


02:51.760 --> 02:57.520
But it's not, you know, it's not a horrible noise, not a whine or anything. The really odd thing is that


02:57.520 --> 03:03.280
where the pump comes in from outside, the hot and cold water coming from outside,


03:03.280 --> 03:09.920
and the cylinder is right behind our living room wall. And the living room radiator is right on the


03:09.920 --> 03:15.520
other side of it. So it basically gets first dibs on any hot water coming in, which meant that this


03:16.240 --> 03:22.720
heat pump circulation, you need a lot more water moving around your system, a lot faster for a heat


03:22.720 --> 03:28.240
pump than you do for a gas boiler. And this is all getting piled through my poor little radiator.


03:28.240 --> 03:34.800
And the noise being made by this radiator, I mean, you know [SSSSH] , to the extent that, you know,


03:34.800 --> 03:39.520
the family's having to turn the TV up to hear over it. And so it took what it turns out that when


03:39.520 --> 03:45.200
the fault went away, they'd fixed the fault, I was able to reduce that. And now it's just like it was


03:45.200 --> 03:50.480
before, effectively. There are some very slight oddities like because it's running, it's actual


03:50.480 --> 03:55.200
water outside, running from outside in the external unit, there's no anti-freeze in it. When the


03:55.200 --> 04:00.560
temperature drops to close to zero, six degrees or below, it circulates the water and runs the


04:00.560 --> 04:06.400
compressor a little bit to stop it freezing, which means that at four in the night or something, you


04:06.400 --> 04:15.520
can hear [sssssh] noise. But it's not bad. It's fine. It's actually no worse than any, it's fine. It's a


04:15.520 --> 04:20.399
fairly nice heating system. But it did take some messing around - took me two months to solve that and I was on the point of writing to Octopus and saying "This is broken, this system. If no one can


04:24.720 --> 04:31.200
hear the TV, it's not working." We also are doing an unusual thing. So as I say, heat pump installers


04:31.200 --> 04:35.680
want you to have all of your radiators on or open all of the time, and all the rooms at the same


04:35.680 --> 04:43.360
temperature. NO! I mean, it's certainly the case that people sleep more comfortably in cooler rooms.


04:43.360 --> 04:48.159
And, you know, when you like us one of your kids has left home, why are you still heating their room? And stuff like that. If you have an absolutely bang-up-to-date Passive House you barely need to


04:55.040 --> 05:01.280
heat it anyway. So I'm with a heat pump installers at this moment. But my formal research shows you


05:01.280 --> 05:07.440
can have TRVs like the ones that are on the end of these radiators with 1-2-3-4-5 and very easily reduce


05:07.440 --> 05:12.480
the heat demand in rooms that you want to be cooler, save energy, save the planet faster, save money.


05:12.480 --> 05:18.880
So has it been saving? So it went in just at the end of November. So ignoring that for each of the


05:18.880 --> 05:24.000
following months, December, January, February, March, April, which we've had bills in for, that bill has


05:24.000 --> 05:31.200
been lower than the corresponding month last year, even though all of those, this month, other than April,


05:31.200 --> 05:36.400
were colder than the same one last year. So it's been colder outside and our bills have been lower.


05:36.400 --> 05:40.000
It's slightly cheating because I was doing complicated [stuff] with our systems before.


05:40.000 --> 05:46.960
But this energy bill for this whole of the last month was 20 quid. And most of


05:46.960 --> 05:52.880
that is standing charge. So that's we've got the PV and so on. But the heat pump was much better


05:52.880 --> 05:58.159
with the battery than I thought it would - with my electrical battery. So I expanded it a little bit last month - I bought a second-hand unit.  Our carbon footprint if you look this is


06:03.840 --> 06:10.960
our graph of our carbon [footprint] from gas and electricity since then. So you can see we made


06:10.960 --> 06:20.560
some effort. We started at six tons.  So here I assumed a fixed carbon intensity, how much carbon


06:20.560 --> 06:26.000
was emitted for every kilowatt hour generated - standard figure up until there. And then I changed


06:26.000 --> 06:32.640
to a SUPER (possibly!) accurate version where every hour I measure our actual whether we are importing or exporting


06:32.640 --> 06:37.280
and what the grid intensity is. So it makes that very little difference. But maybe it said we went


06:37.280 --> 06:42.880
slightly positive. I think we'll get come down and go negative again. And I had an idea yesterday


06:42.880 --> 06:50.640
in the bath as one does - I can knock another 10% off. So the cost [that] Octopus originally quoted


06:50.640 --> 06:55.440
as two thousand seven hundred in the end, I think partially to get rid of me, partially because I only


06:55.440 --> 07:00.960
wanted one radiator change, was two thousand five hundred. Octopus' target has been to get it down


07:00.960 --> 07:06.320
cheap enough that it's actually free. They are trying to make it possible to have no CAPEX and


07:06.320 --> 07:13.760
no OPEX (no bills). That's their target. Realistically, if you go to someone like Leah of Your Energy,


07:13.760 --> 07:17.680
Your Way, she'll tell you she can't get anywhere near Octopus because they're throwing a huge


07:17.680 --> 07:24.240
invisible subsidy in on top of the government. But a few thousand quid, which is roughly what it takes


07:24.240 --> 07:31.120
to put a new combi in - a condensing combi - is what you can expect. I mean, that grant is designed to


07:31.120 --> 07:37.920
make it no more painful than than putting a new gas boiler in, except for the disruption involved.


07:37.920 --> 07:41.760
Was it quick? Well, as I say, depending on how you measure it, there's the last time I had a


07:41.760 --> 07:44.800
Secretary of State for Energy in my house. I'm sure it happens to you all the time.


07:45.520 --> 07:51.440
And I had color in my hair - and it was 12 years. That's when I wanted to do it. So I would have


07:51.440 --> 07:58.400
been slightly behind Peter, but not much, in putting one in. I think getting in the queue,


07:58.400 --> 08:02.320
there aren't enough installers around. So you can't just phone up and have it done instantly.


08:02.320 --> 08:07.600
There are more works to be done. In this open letter to the Secretary of State and so on I'm going to say


08:07.600 --> 08:12.480
"This is how I think you could make it happen in two days for most installations." If it costs the same as


08:12.480 --> 08:18.720
a gas boiler, costs the same to run as a gas boiler as well, and you can do it in two days, why wouldn't


08:18.720 --> 08:23.040
you put in a heat pump, unless you believe the Daily Mail horror stories that it's going to make your


08:23.040 --> 08:32.400
children go trans or something - I don't know. Should be two days. So, space taken. So we had the


08:32.400 --> 08:37.840
the thing on the left, we had the combi boiler in here before, and I have a heat battery as well, which is sitting down here... If we didn't have the heat battery we'd just about - just about - have


08:43.760 --> 08:50.720
got the hot water tank inside there, we could have stayed in roughly in the same space -


08:50.720 --> 08:57.520
we'd have lost some cupboard space. All that needs to be in the house these days is a hot water tank.


08:57.520 --> 09:03.280
The reason we all loved combis is they were instant hot water,


09:03.280 --> 09:07.520
which never runs out. You didn't need hot water tank. And so people's airing cupboards got, you know,


09:07.520 --> 09:12.720
recovered for other purposes. So you need to have one back with a heat pump. However,


09:12.720 --> 09:18.000
I've got a heat battery. We've got a water tank. You can see the top of the thing sticking out of the


09:18.000 --> 09:24.320
top here. This is our replacement. You put all the gubbins inside. And if you go right back to the


09:24.320 --> 09:29.280
front [page], that is the thing outside, which is about the size of a moped. And I took this


09:29.280 --> 09:34.400
picture because it's interesting because it was just frosting up. So an interesting thing that


09:34.400 --> 09:38.320
happens in the UK is you spend a lot of time with the temperature just above zero and quite a lot


09:38.320 --> 09:46.560
of humidity in the air. And so you get frost on the fins and the system has to do a defrost cycle.


09:46.560 --> 09:54.240
It's quite spectacular. It's a plume of steam coming out of the thing. It's quite spectacular.


09:54.240 --> 10:00.240
You don't get that with the old boiler. It should be that if you have a boiler which fails


10:00.240 --> 10:03.920
in December, you're going to say, could you please repair it, or can I have like-for-like?


10:03.920 --> 10:12.560
Because you understand that. It took me 12 years or eight months or two months or whatever it is,


10:12.560 --> 10:19.120
to get mine in. And I had to do a lot of external works. So we've got to get over this. I wrote 22,000


10:19.120 --> 10:24.560
words on the process. [] When you've got a gas boiler,


10:24.560 --> 10:29.440
you've basically got two controls that you can touch. One is the temperature your radiators run at,


10:29.440 --> 10:35.440
and one is the temperature your hot water runs at. My heat pump's got something like 50 parameters.


10:35.440 --> 10:39.920
Now you don't normally get to see all of them. And I am doing PhD, and I've looked,


10:39.920 --> 10:45.360
but I've written 7,000 words on all the changes I've made to those parameters. And the aim of my


10:45.360 --> 10:50.160
research, which is improving home heating decarbonisation, so we can actually do it properly,


10:50.160 --> 10:54.240
is how can we make it as simple as [possible] - people didn't run their gas boilers properly - we have


10:54.240 --> 10:58.800
to make it simpler than running a gas boiler, and less disruptive, and no more expensive. And I


10:58.800 --> 11:03.680
believe all of those things can be done without huge changes to the way people are working.


11:03.680 --> 11:05.840
We just need to think about it very differently.