00:00.000 --> 00:05.920
Okay, hello everybody. We installed a heat pump, well it's nearly 15 years ago now, so we were


00:05.920 --> 00:11.920
distinctly early adopters of this, and it was really part of a project to try and reduce our carbon footprint, so no calculations about payback period or anything like that.  I divided it into "What is a heat pump?" ... there is so much


00:20.880 --> 00:26.320
misinformation and disinformation around heat pumps, just try and get everybody on the same


00:26.320 --> 00:33.920
same place. "Our experience with owning and living with one of these things for 15 years" and then "Why


00:33.920 --> 00:40.240
heat pumps are necessary" really for the country, not just for individuals, so a heat pump. Okay,


00:40.240 --> 00:45.360
well most people are absolutely shocked at this price and really when you start to look into them


00:45.360 --> 00:51.760
they are extraordinarily complex engineering devices, much much more complicated than a boiler,


00:51.760 --> 00:57.200
stuffed full of electronics, compressors, heat exchangers, all sorts of things and you think


00:57.200 --> 01:03.200
they're very sort of new things but they're not. The first heat pump was made in 1830, well before


01:03.200 --> 01:10.400
anybody thought about gas boilers.  You all, each of you, probably has three heat pumps, maybe more.


01:10.400 --> 01:16.400
You've got one in the fridge, one in the freezer, one in a car, you might have an air conditioning


01:16.400 --> 01:21.840
and you might have dehumidifiers. They are everywhere, it's very common technology now, but


01:21.840 --> 01:30.320
complicated. Basically what it does is that it pumps heat backwards against temperature. I mean


01:30.320 --> 01:33.520
you'll think about your fridge, this is what happens, you know, your fridge, you're making a fridge


01:39.200 --> 01:43.600
and the fridge keeps on pumping it out and dumping it back in the kitchen and it's just going round


01:43.600 --> 01:48.960
and round in circles and that's what heat pump does. It needs some electricity to work because


01:55.200 --> 02:00.800
a gas boiler, the gas boiler or electric heater, you buy the electricity or the gas, you put it in,


02:00.800 --> 02:06.480
that's got the energy in it and you release it as heat. So you take the chemical energy in the gas


02:06.480 --> 02:13.040
and convert it into heat energy, um, the efficiency is maybe 80 or 90 percent, some of it's waste,


02:13.040 --> 02:18.880
some of it goes to the gym and that's fine. With a heat pump, you're not actually converting one


02:18.880 --> 02:23.760
form of energy to the other, you're harvesting energy in the environment and pumping it into


02:23.760 --> 02:29.360
your house. It takes some energy to run the machine and that energy is not wasted, it is, most of it is


02:29.360 --> 02:37.120
retained in the system, so it's not wasted energy, um, but the efficiencies are huge because it's,


02:37.120 --> 02:42.240
instead of being saying 90 percent for a good gas boiler, it's 300 percent for a heat pump,


02:42.240 --> 02:46.720
so it's harvesting three times as much. Now, when I sort of mentioned it, everybody said,


02:46.720 --> 02:50.960
well what happens on a really cold day when it's freezing, surely there's no energy left in the air.


02:50.960 --> 02:56.720
Um, well there is lots of energy left in the air, um, you have to think that there is no energy


02:56.720 --> 03:03.760
left in the air at minus 273, which is absolute zero. Now, you wouldn't exist in that form at


03:03.760 --> 03:09.040
minus 273, but if you think that you're, the environment we live in, it's maybe, you're going


03:09.040 --> 03:15.520
to be using a heat pump from when it's about 10 degrees to minus 5 degrees here, and the change


03:15.520 --> 03:21.360
in energy in the air over that range, tiny. The temperature difference does affect the heat pump,


03:21.360 --> 03:26.880
but it doesn't affect the principle of there being lots of energy in the environment to be harvested.


03:26.880 --> 03:33.920
So these are strange devices, um, very reliable, established technology. We went for a heat pump,


03:38.880 --> 03:44.960
your house. I thought, well okay, so we better check this. So we went to Daikin's training


03:44.960 --> 03:49.440
centre in Woking, where they got lots and lots of heat pumps, and we heard them. They sent them


03:49.440 --> 03:54.720
running, and we listened to them, and we thought, well okay, they're not silent, they make a noise,


03:54.720 --> 04:00.160
and it's probably a bit noisier than the flu on a gas boiler, because gas boiler makes noise,


04:00.160 --> 04:05.600
um, but it's okay, it's going to be okay, or we can live with it. And anyway, what's the equation


04:05.600 --> 04:10.720
between climate change and a bit of noise, why these two equated, I don't know why they equated,


04:10.720 --> 04:18.640
but people do. It was installed, um, we were the first customers in this company, and it showed they,


04:18.640 --> 04:23.840
um, we had three guys. We had a guy who dealt with refrigerants, a guy who dealt with electrics,


04:23.840 --> 04:28.640
and a guy who dealt with plumbing, and they were very good, but they never done one before,


04:28.640 --> 04:35.680
and they fled after they'd fitted me, and left me with a manual. This, they translated from


04:35.680 --> 04:42.000
Korean, I suppose, and my first was like, how on earth can they sell these to the general public?


04:42.000 --> 04:46.240
You have to be, I'm an engineer, and I have to be an engineer really to cope with this. I find it


04:46.240 --> 04:50.400
very stressful, very difficult, and I find faults, and they have to come back, and you know, I had to


04:50.400 --> 04:54.960
commission it and get it running, but we've got it settled, and I think if you went to Octopus now,


04:54.960 --> 05:00.160
who are the big sellers of them, it will be absolutely fine. Okay, it's been reliable,


05:00.160 --> 05:05.760
it had its first fault a couple years ago. In fact, it was a trivial fault. It took quite a


05:05.760 --> 05:10.880
lot of money to fix it, because the diagnostics in the machine are not brilliant. Ours is a very


05:10.880 --> 05:17.280
early one, and when it came out with its error code, and I phoned Aiken and said this is the


05:17.280 --> 05:22.800
error code, and he said, oh dear, that one covers a whole lot of faults, and we can't really tell.


05:22.800 --> 05:29.200
And so they changed lots of parts, which they didn't need to change, but I think machines,


05:29.200 --> 05:35.200
you know, it's all got better now. It was really just a solenoid that got a bit sticky, and it


05:35.200 --> 05:40.000
actually went into, like cars do, a limp home mode. So it carried on working, so this was in mid-winter,


05:40.000 --> 05:47.440
but it carried on working, not very well, but it kept our house warm over that time. So, and I have


05:47.440 --> 05:54.320
its checked every year, it doesn't really have any requirements for servicing, very, very simple.


05:54.320 --> 05:59.440
And the people who come and service it, they're really, they're absolutely excellent people.


05:59.440 --> 06:06.400
That was cost, well, in 2009, cost 12,000 pounds, so very expensive compared to gas boiler


06:06.400 --> 06:12.640
at the time. This is the crux of it, really, a graph of the efficiency and how the efficiency


06:12.640 --> 06:19.680
varies with the temperature of the water. Because it really is just a straight replacement for a gas


06:19.680 --> 06:24.880
boiler, in our case. So it connects into a hot water regulator system, which I've come on to,


06:24.880 --> 06:34.240
and the vertical bit is the efficiency, and it goes from four times to two times. So 400% efficiency,


06:34.240 --> 06:41.920
down to 200% efficiency, and this is the difference in temperature between hot water in the radiators,


06:41.920 --> 06:46.800
so that's what it's producing, and the temperature outside, because the temperature outside


06:46.800 --> 06:54.080
affects how it works. And what this means is on temperate days, when it might be seven degrees


06:54.080 --> 06:58.159
outside, and you want to heat your house to 20 degrees, and you might need water in the


07:05.760 --> 07:11.120
five, and you want to get water in the radiators up to 50 degrees, the efficiency drops. So the


07:11.120 --> 07:16.160
efficiency of it is changing rapidly all the time. It's not like a gas boiler, which is pretty


07:16.160 --> 07:22.560
constant. This is dynamic. It's moving around the whole time, depending on how cold it is outside,


07:22.560 --> 07:29.040
and how warm the radiator needs to be. So with this sort of thing in mind, you need to really


07:29.040 --> 07:34.800
try to get it to run as cool as it can all the time. So it's not like a gas boiler, which is


07:34.800 --> 07:41.040
blast water, hot water at 70, 75 degrees. Shouldn't really do this, but they do. This you need to


07:41.040 --> 07:46.240
always think about getting the temperature of the water down as low as possible, because the


07:46.240 --> 07:51.760
efficiency rockets you do that. And this I think this is why, you know, there's so much criticism


07:51.760 --> 07:56.960
in the press of people finding fault is because they haven't been installed with this in mind.


07:56.960 --> 08:02.000
The temperature of the water has to be as low as possible. And if you lower the temperature of the


08:02.000 --> 08:07.360
water and the radiators, the output of the radiators goes down more rapidly than the


08:07.360 --> 08:13.200
temperature that goes down. It's not linear, so it can go horribly wrong if you don't get it right.


08:13.200 --> 08:17.840
And there are two ways of addressing getting the temperature down. One is you improve the efficiency


08:17.840 --> 08:22.400
of the insulation in your house, which you might or might not be able to do. And that people say,


08:22.400 --> 08:27.600
you know, insulates your house. Well, okay, but you can put some loft insulation in, you can put


08:27.600 --> 08:33.840
some better windows in, some draft proofing around the doors. And then it starts to get difficult.


08:39.280 --> 08:44.320
insulation, but if you've got an old house with solid brick walls, it becomes very expensive.


08:44.320 --> 08:48.640
It's a Victorian house, you start to change the character of the house if you put it on the outside.


08:48.640 --> 08:56.480
There's just a heat pump. It's an easy fix, really, because what you do is you reduce your energy


08:56.480 --> 09:02.480
consumption three times. And there's no insulation, which you can do to a Victorian house, which will


09:02.480 --> 09:08.160
get anywhere near that. And if you did try it, it would cost you hundreds of thousands of pounds,


09:08.160 --> 09:12.240
you know, make sure you're loft insulation, fine, make sure you've got the windows draft proofing,


09:12.240 --> 09:16.720
maybe you can seal the floor. So you haven't got lots of drafty floors, and then stick a heat


09:16.720 --> 09:22.160
pump in. That's the best thing. There are settings in our machine, which you have to go in and set.


09:22.160 --> 09:27.200
I'm not showing the installer should do this is where you actually set the temperature in the


09:27.200 --> 09:33.360
radiator to be dependent on the temperature outside. So on really, really cold days, our


09:33.360 --> 09:39.680
radiators are about 50 degrees, maybe that's 49. And that's as hot as they go. And then as we come


09:39.680 --> 09:44.480
into this time, well, it's not on now. But you know, a few months ago, when it was maybe 10 degrees


09:44.480 --> 09:49.600
outside, I would have the temperature and the radiators about 2022. And what that does is


09:49.600 --> 09:53.920
because the pump's compressor now doesn't have to work so hard, because he's not having to produce


09:53.920 --> 10:01.440
very hot water. The electric demand drops and the efficiency rockets. And this is what we did, we


10:01.440 --> 10:07.600
put in bigger rate, we had steel radiators. And at the time we did this the best way, because


10:07.600 --> 10:11.600
everybody has a problem, they have pipes coming up to the floor, and what are you going to do to tear


10:11.600 --> 10:17.920
up the floor to put in bigger radiators. So we went for fitting radiators to the same pipes.


10:17.920 --> 10:23.680
And we went for cast aluminium radiators. So instead of having a steel panel radiator,


10:23.680 --> 10:29.920
we put in cast aluminium radiators, which is like this and this, which have much higher output.


10:29.920 --> 10:35.600
Basically, you need to be doing something like increasing, well, it depends on what you've got


10:35.600 --> 10:41.280
in the house, but you may be looking to increase the radiator outputs by 50 to 70%. Something of


10:41.280 --> 10:48.000
that order is likely to work. If you take a radiator, steel radiator, which is designed to


10:48.000 --> 10:54.560
work with water going in at 70 degrees, and then you then change that and put water in at 50 degrees,


10:54.560 --> 10:59.600
the output of the radiator will be hard. Now, since we did this, which was obviously 50 years ago,


10:59.600 --> 11:06.560
Stelran, who are the big manufacturers of steel radiators, now produce a radiator, which is


11:06.560 --> 11:12.800
designed to go onto the existing pipes and have twice the output. So they have actually solved


11:12.800 --> 11:19.040
this problem, but we didn't have that choice. So on our pipe, you can probably see just about,


11:19.040 --> 11:23.840
there's a sort of conch of botch pipe workers, the plumber, the pipes didn't quite line up with


11:23.840 --> 11:27.040
the size of the radiator, and the plumber had to do with the chicken was around.


11:27.040 --> 11:34.720
You wouldn't need to do that nowadays. So one of the things, if you can add insulation and reduce


11:34.720 --> 11:38.800
the heat loss of your house by doing that and draft quickly and get that improvement,


11:38.800 --> 11:44.320
sort of reducing airflow, sweeping heat out through the house, you might reduce, say,


11:44.320 --> 11:49.040
the heat demand of the house by 10%. If you could do that with a heat, if you do that with a gas


11:49.040 --> 11:54.000
boiler, you can just save 10%. If you do it with a heat pump, what it means is you can take the


11:54.000 --> 11:58.720
opportunity to lower the temperature in the radiators because you no longer need so much


11:58.720 --> 12:03.760
heat flowing into the house. You lower the temperature in the radiators and the efficiency


12:03.760 --> 12:11.200
goes up. So you probably save 15%. Our energy bills are energy consumption normalized. It's


12:11.200 --> 12:17.920
about 50 kilowatt hours of energy. This is everything we use. So I can't separate out


12:17.920 --> 12:22.960
televisions left on standby and all this sort of stuff, because we just can't be bothered to sort


12:22.960 --> 12:31.360
that out. It's about 50 kilowatt hours per square meter. And UK norms are 150 to 300 kilowatt


12:31.360 --> 12:33.800
hours per [square] meter, maybe more, depending...