Going back to the before times, 2019, when we just had [an] ordinary boring gas


00:07.440 --> 00:12.400
combi boiler and it wasn't condensing, we've had it since we moved into the house about 20 years ago.


00:12.400 --> 00:18.800
Boring gas [] combi boiler, but we've got aerogel wall insulation and the superb Radbots,


00:18.800 --> 00:25.120
and four of us at home and we consumed about 3.1 megawatt hours in gas that year.


00:25.120 --> 00:33.280
For reference, the Ofgem 2017 low gas typical domestic consumption value, was 8 megawatt hours


00:33.280 --> 00:37.440
a year. So we were low and we weren't cheating by heating on the sly with electricity. Our


00:37.440 --> 00:42.560
electricity gross consumption if we had had no solar PV was 2 megawatt hours for that year


00:42.560 --> 00:50.000
compared to the Ofgem 2017 low class 1, which means when you're not heating with electricity


00:50.000 --> 00:56.640
of 3.1 megawatt hours per year. So we were low on both scales. Class 2 users may be all electric


00:56.640 --> 01:02.880
heating with storage heaters or whatever and high is much higher for class 2 in that one. Net exports


01:02.880 --> 01:08.480
were about 1.9 megawatt hours for that year. A little thing called the pandemic stopped me


01:08.480 --> 01:12.960
putting in the Thermino.  I was ready to go in early 2020 but kind of it didn't seem the to be the most important thing to be doing at that moment.  But finally, it got round to 2022, and in March


01:19.360 --> 01:24.320
the Thermino and the Eddi went in. So for reference in case any of you don't know,


01:24.320 --> 01:29.120
when I started this thing this Sunamp product line was called Uniq. By the time I'd actually


01:29.120 --> 01:34.000
got around to doing it in 2022 it was called the Thermino and I went for a size equivalent to


01:34.000 --> 01:42.880
about 150 litres water tank and the Eddi, the myEnergi Eddi, which I wanted to use for a solar


01:42.880 --> 01:47.920
diversion but also because it was highly controllable remotely and there's some nice stuff on the


01:47.920 --> 01:54.479
Internet, people showing how to do it, so that I could choose to top up the Thermino when there were low grid [carbon-intensity] times.  So the first curiosity when I got the Thermino was that when I filled it up


01:58.560 --> 02:03.520
the first time nominally it holds seven kilowatt hours roughly but when you're but that's when it's


02:03.520 --> 02:08.000
hot so you draw that seven kilowatt hours worth of heat and it's still just hot enough whatever


02:08.000 --> 02:13.760
that means I think 45 degrees or something. When you're heating from cold mains water in March


02:13.760 --> 02:19.520
actually it's more like 10 kilowatt hours and ours [DHW consumption] is about four kilowatt hours a day so that implies it's just short of two days' worth which is just about right.  But anyway there's a very clever valve which we have in our system called the Intasol valve which is entirely mechanical -


02:28.160 --> 02:32.880
there's no electronics, computing, Internet, anything.  So it's designed to work with a


02:32.880 --> 02:38.000
combi and a thermal water store and our Thermino looks like a solar thermal water store to it.


02:38.000 --> 02:42.240
If the output of that when you turn on tap if the output is from that is hot enough it just uses


02:42.240 --> 02:47.280
water straight from that although it then has a tempering valve to cap the temperature at 50


02:47.280 --> 02:52.880
degrees to prevent scalding. If the water from the Thermino is not hot enough to use directly, ie


02:52.880 --> 02:58.320
it's below about 50 degrees it routes it very cleverly it mixes it down to 28 so any


02:58.320 --> 03:03.920
combi will accept it and feeds it into the Thermino so it bleeds residual heat into the


03:03.920 --> 03:08.800
combi to reduce your demand so you really get that 10 kilowatt hours of storage. So in fact


03:08.800 --> 03:12.720
therefore internally my measure that I'm not allowed to share with you because of an NDA with


03:12.720 --> 03:20.560
Sunamp shows between zero and 100% [well] minus 30 and 100% well actually 110% because you can


03:20.560 --> 03:24.880
overfill it with diversion a little bit get a little bit more in and I don't do that when


03:24.880 --> 03:29.280
I'm topping up from the grid so it means that if there's ever some sunshine I don't expect


03:29.280 --> 03:34.160
it can still be absorbed by the system. Our DHW demand about four kilowatt hours a day is


03:34.160 --> 03:39.360
something like a megawatt hour a year and with diversion about half of that so basically all of


03:39.360 --> 03:45.600
summer and some of the shoulder months is covered.  It's 500 kilowatt hours a year.  And if you look at


03:45.600 --> 03:50.640
the chart you'll see the green bars are where it's diverting (this is for September in the year it


03:50.640 --> 03:55.680
went in 2022) and you see the start of September it's basically all green and that shows we were


03:55.680 --> 04:00.720
using water most days right so that it was topping it up but then towards the end of the month we're


04:00.720 --> 04:06.400
starting to use boost. The boost top up from the grid but it's complicated it says what's the


04:06.400 --> 04:10.240
threshold.  The black is what's the threshold for grid intensity I'm going to use for allowing top


04:10.240 --> 04:16.480
up.  The green and sort of yellow squiggly line near the bottom is grid intensity actual grid, so grid means it's 'super-green' which means it's in the bottom quartile


04:22.000 --> 04:28.480
for the last week and there is no storage being drawn down into the grid which means probably


04:28.480 --> 04:34.480
the storage is topping up so maybe we should too.  And the little yellow plus signs are samples


04:34.480 --> 04:39.440
where the Thermino is indeed being topped up.  Interestingly the little black crosses are when I


04:39.440 --> 04:43.920
respond to dips in grid frequency and stop topping up so I'm providing a tiny amount of grid


04:43.920 --> 04:49.360
frequency support as well.  And as I gained more confidence in this I made the boost algorithm


04:49.360 --> 04:55.120
more aggressive so for example last year we basically drew almost no gas for hot water - only


04:55.120 --> 04:59.520
for space heating - so only in the winter so we basically had zero effectively zero gas bills


04:59.520 --> 05:04.640
other than standing charge most of the year and that's only done as I say oh there's a an actual


05:04.640 --> 05:13.120
cap on this top up of being 170 something grams of CO2 per kilowatt hour so it will only top up


05:13.120 --> 05:18.160
when it's less carbon to top up the Thermino and use it from there than it would be by burning gas


05:18.160 --> 05:22.400
directly.  So our footprint is lower than it would have been we used virtually no gas and it all got


05:22.400 --> 05:28.080
turned off when we were capped at the end of November... So ...
The Present - Heat-pump and Eddi ...
so ...


05:28.080 --> 05:33.360
At the end of November, well at the start of November middle of ... November, we disconnected the


05:33.360 --> 05:39.920
Thermino from the combi so that when Octopus would come in they would just have a plain combi system


05:39.920 --> 05:44.720
to upgrade but various things to try and make sure that it would all go back together again.


05:44.720 --> 05:48.800
Well it hasn't it's not perfect we're going to have to do more work than I wanted to but it's OK.


05:48.800 --> 05:55.440
But for the moment we have a relatively vanilla Daikin heat pump with water cylinder curiously


05:55.440 --> 06:02.960
160 litres nominal so nominally the same capacity as the Thermino but three times the size and we


06:02.960 --> 06:09.920
have DHW, domestic hot water, and space heating from that and it's running right now.  The interesting


06:09.920 --> 06:14.800
thing is that generally for electricity ignoring anything to do with PV or whatever and ignoring


06:14.800 --> 06:20.720
heat we use about five kilowatt hours of electricity per day in the house and the space heating and


06:20.720 --> 06:24.800
domestic hot water together via the heat pump is coming to about the same day so it's roughly


06:24.800 --> 06:28.320
doubling our electricity consumption.  Which is fine.  It's probably going to be true for the whole of


06:28.320 --> 06:33.040
this month it doesn't look like it's going to get much colder.  This is a sort of mildish month.  So


06:33.040 --> 06:40.400
the Eddi was driving [the] Thermino via its heater output one and we diverted that instead to control the


06:40.400 --> 06:49.040
immersion heater on the hot water tank.  So normally once a week the heat pump system is programmed to


06:49.040 --> 06:55.440
use the immersion heater to raise the whole hot water tank to about 60 degrees C to ensure that


06:55.440 --> 07:00.240
any legionella is killed.  Now, you don't need to do it once a week some people do once a day some


07:00.240 --> 07:05.120
people keep it permanently at 60 - you don't need to do that.  We probably turn over half the tank


07:05.120 --> 07:12.080
volume every day and none of us except possibly me as the oldie in the house are in any way


07:12.080 --> 07:17.840
vulnerable.  I do baths rather than showers anyway and so I have now modified it to be a bit smarter


07:17.840 --> 07:23.520
which says it waits eight days since the last time the tank was at maximum temperature and then in a


07:23.520 --> 07:31.520
slot in the morning between midnight and 6am if we get to super green it will then run the


07:31.520 --> 07:37.120
pasteurisation cycle then which takes about three kilowatt hours.  If that hasn't happened by 14 days


07:37.120 --> 07:41.760
in - and I could push that out if I was feeling like it - if that hasn't run by 14 days


07:41.760 --> 07:47.920
it forces one the next morning.  Now, that reduces the overhead.  If I were running a pasteurisation


07:47.920 --> 07:53.600
cycle every day that would be throwing away about well that would be heating putting in about three


07:53.600 --> 07:59.520
kilowatt hours of heat at a CoP [Coefficient of Performance] of 1.  By doing it every sort of 10 days I expect this to be it's an


07:59.520 --> 08:05.440
average of 0.3 kilowatt hours per day at a CoP of 1 and the rest of the CoP of I reckon I'm


08:05.440 --> 08:11.280
estimating them between two and 2.5 or better so it's diluting that a lot less and it's doing when


08:11.280 --> 08:19.120
when grid intensity is low it's nice on the grid demand is low.  On my Eddi I have - I had - a spare


08:19.120 --> 08:26.000
slot for a current clamp and so I put on a second one for that to monitor the entire supply to the


08:26.000 --> 08:32.640
heat pump so the H4 boundary.  And interestingly even [the] little OpenTRV box and so on are all supplied


08:32.640 --> 08:37.600
via that even though it goes out the front of the house to the heat pump, through the heat pump, down


08:37.600 --> 08:41.600
underground, through the wall, and all the way around the side of the kitchen, it's all supplied from


08:41.600 --> 08:46.000
there.  And when it's quiescent so when it's not doing any heating of any sort hot water or space heating


08:46.000 --> 08:51.520
that's using about 10 or 11 watts which is not bad.  Interestingly the circulation pump on its own


08:51.520 --> 08:56.720
adds about another 50 watts.
And I've set out with this heat pump that it is not [connected to the Internet] because at the moment


08:56.720 --> 09:01.680
doesn't need to be connected I've set it up all sensibly statically so for example it keeps the


09:01.680 --> 09:10.320
hot water at 45 degrees basically from 7-ish 7:30 in the morning till 4 pm and then from 7 pm


09:10.320 --> 09:17.120
till 9:30 the rest of the time it will keep it to 42 degrees so we use less hot water at peak times


09:17.120 --> 09:22.320
heating electricity for hot water.  My son just ran a bath 10 minutes to four so it kind of nearly


09:22.320 --> 09:28.320
defeated the mechanism just now but it still uses less. Radbots are controlling call for heat for the


09:28.320 --> 09:33.600
space heating and it's an on-off thing and many installers will absolutely hate that.  And I wrote


09:33.600 --> 09:38.320
my first academic paper about why we should microzone and why TRVs should be fine but they


09:38.320 --> 09:42.560
also would absolutely hate the fact that it's microzoned and not running all the time.


09:42.560 --> 09:48.880
(I think I can get all these 3D graphs on at once.)
The top one is temperatures as seen by the Radbots themselves


09:48.880 --> 09:53.120
on the TRV so [] the temperature doesn't wave around quite as much as that.  That's


09:53.120 --> 09:58.640
a temperature [] right next to the radiator. Bottom trace is a spare Radbot I shoved


09:58.640 --> 10:04.080
outside in our porch and interestingly it now gets the cold breeze from the from the heat pump


10:04.080 --> 10:09.360
so it's a lot more wobbly temperature than it used to be. The next one down with a purple line shows


10:09.360 --> 10:14.800
call for heat to the heat pump and you see it's only on about maybe a third of the time.  And when


10:14.800 --> 10:21.120
we get down to design temperature at minus two degrees outside which will be about three times


10:21.120 --> 10:27.040
the heating degree days I think that won't quite get up to 100.  But an interesting point running it


10:27.040 --> 10:32.320
like this is if I ran it all the time the way the installers would like me to I'd be spending a


10:32.320 --> 10:38.640
kilowatt hour a day just running the pump. I'm spending I'm saving two thirds of a kilowatt hour


10:38.640 --> 10:43.920
just on not running the pump so I could have a slightly less good CoP and still be ahead by


10:43.920 --> 10:49.200
by avoiding that parasitic load. There are options in the Daikin to only sample running and so on.


10:49.200 --> 10:55.120
Anyway, next graph is percent open each of the TRVs and when it's over over 49 then it's calling for


10:55.120 --> 11:01.040
heat.  So this is in the week coming up to a few days ago.
What's in the future?
I'll [reconnect] the


11:01.040 --> 11:06.560
Thermino. I'll change the algorithm for top up to say that when the current grid intensity is about


11:06.560 --> 11:12.880
a factor of two or better lower than the average for the last seven days or the carbon intensity


11:12.880 --> 11:17.840
dot org national grid prediction for the next two days then I will top up the Thermino on the grounds


11:17.840 --> 11:24.800
that although I'm topping them up with CoP 1, immersion electricity, actually I'm gaining a


11:24.800 --> 11:29.680
factor of two because I'm storing energy now that I do not have to get from the grid when


11:29.680 --> 11:32.240
the intensity will be higher later.